ACV Thermostat+reset 54764009
SKU 54764009
Marca ACV
Foto
Specifiche principali
| Switching temperature | 103 °C |
|---|---|
| Capillary length | 1500 mm |
| Bulb diameter | 6 mm |
| Reset type | manual |
| Manufacturer code | 54764009 |
| connection_type | two-wire |
| Safety feature | overheat protection |
56,42 EUR
51,29EUR
disponibile · 2
IVA 21% inclusa · 42,39 EUR escl. IVA · spedizione calcolata al checkout
- Spedizione mondiale dal magazzino
- Ricambio originale del produttore
- Spedizione entro 24 ore per articoli in magazzino
Descrizione
The ACV Thermostat+reset 54764009 is a mechanical safety limit device with a manual reset, designed to protect boilers from overheating. It opens its contacts when the sensed temperature reaches the factory-set switching point of 103 °C. The thermostat features a capillary length of 1500 mm and a bulb diameter of 6 mm. It uses a two-wire connection and is compatible with ACV Prestige 32 MK2 and Prestige 50 MK2 models. The manufacturer code is 54764009.
Ulteriori dettagli
| Compatible with | Prestige 32 mk2, Prestige 50 mk2 |
|---|---|
| Installation type | installed in the water or flue gas flow path |
Scelta e montaggio
Parts of this type are selected by switching temperature, capillary length, bulb diameter, and reset mode. When replacing, ensure the bulb makes good thermal contact with the sensing surface, and check that the capillary is free of kinks or cracks. The two-wire connection is typically normally closed, so a fault in the cable or sensor will open the safety chain.
Segni di guasto
Common failure modes include a drifting switching characteristic, which can cause nuisance trips or failure to protect, and a broken capillary, which renders the thermostat inoperative. If the thermostat trips, the system will not restart automatically due to the manual reset, requiring an engineer to press the reset button after resolving the over-temperature cause.
Compatibile con
ACV Prestige 32 MK2, Prestige 50 MK2 Prestige 32 MK2 Prestige 50 MK2ACV Prestige 32 mk2ACV Prestige 50 mk2
Tutte le specifiche
| Switching temperature | 103 °C |
|---|---|
| Capillary length | 1500 mm |
| Bulb diameter | 6 mm |
| Reset type | manual |
| Manufacturer code | 54764009 |
| connection_type | two-wire |
| Safety feature | overheat protection |
Codici
| SKU | 54764009 |
|---|---|
| Additional article | 129.805.004 |