Key specifications
| Safety time | 5 s |
|---|---|
| Flame loss reaction time | less than 1 second |
| Independent safety contacts | 2 contacts |
| Firing stages | single-stage |
| Cycle type | intermittent (cyclic) |
| Maximum oil burner throughput | 30 kg/h |
| Compatible burners | Riello, Baltur, Weishaupt, Lamborghini |
| Air supply | forced draft |
| Flame detection methods supported | ionisation, UV, or IR |
| Pre-purge time | 20 s |
Lowest price in the 30 days before the price drop
108.48EUR
in stock · 2excl. VAT · import VAT and duties on delivery · shipping calculated at checkout
- Delivery to 97 countries
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Brahma 18049001 is a microprocessor-based control box for single-stage forced-draft liquid fuel burners, operating in intermittent (cyclic) mode. It has a pre-purge time of 20 seconds and a safety time of 5 seconds, with a flame loss reaction time of less than 1 second. It supports flame detection via ionisation, UV, or IR methods and includes two safety contacts. It is compatible with burners from Riello, Baltur, Weishaupt, and Lamborghini, and is suitable for oil burners with a maximum throughput of 30 kg/h.
Further details
| Application | boiler equipment, heat generating equipment, industrial installations, specialized equipment |
|---|---|
| Application Type | automate ignition, flame monitoring and safe shutdown of liquid fuel burners |
| Flame Detector | photocells FC11, FC13, FC14 or FC14L |
| Fuel Type | liquid fuel (diesel or heavy oil) |
Choosing and fitting
When selecting a control box of this type, verify that the supply voltage, safety time, pre-purge time, and flame detection method match the original. Ensure the wiring base or plug connector is compatible, as controls are not interchangeable across different series. Check the burner's specifications and the appliance manual to confirm the required parameters.
Signs of failure
Common failure modes include failure to ignite, lockout after the safety time, or immediate shutdown upon flame loss. The equipment may show a fault code or fail to start. Check the flame detector, wiring connections, and the control box's internal fuse or relay for issues.
All specifications
| Safety time | 5 s |
|---|---|
| Flame loss reaction time | less than 1 second |
| Independent safety contacts | 2 contacts |
| Firing stages | single-stage |
| Cycle type | intermittent (cyclic) |
| Maximum oil burner throughput | 30 kg/h |
| Compatible burners | Riello, Baltur, Weishaupt, Lamborghini |
| Air supply | forced draft |
| Flame detection methods supported | ionisation, UV, or IR |
| Pre-purge time | 20 s |
Part numbers
| SKU | 18049001 |
|---|---|
| Additional article | 246.124.024 |