1660.80 EURexcl. VAT · import VAT and duties on delivery
Kromschroder Burner control unit BCU370WFEU0D3 88600123
Brand Kromschroder
Key specifications
| Supply voltage | 230 V |
|---|---|
| Safety time | 1 s |
| Flame detector type | UV sensor or ionisation sensor |
| Protection class (IP) | IP54 |
| Body material | impact-resistant and heat-resistant plastic |
| Flame control mode | ionization control or UV control |
| Burner capacity | unlimited capacity |
| Ambient temperature | -20–60 °C |
| Service life under maximum load | 250000 |
| Cycle type | intermittent or continuous |
| Flame detection methods supported | ionisation, UV |
| Safety feature | fault lock-out |
| Controller enable signal delay time tRF | 0 s |
| TC test period tP | 60 s |
| Fan run-up time tGV | 0 s |
| Fan control rating | 3 A |
| Maximum length of ignition cable with integrated electronic ignition | 1 m |
| Maximum length of ionisation/UV cable | 50 m |
| Air monitoring during pre-purge | on |
| Air monitoring during operation | on |
| Gas pressure monitoring | on |
| UVS check | off |
| Operating time in manual mode | 5 minutes |
| V2 during burner operation | off |
| Behaviour in the event of flame failure during operation | fault lock-out |
| Burner switch-off threshold | 1 µA |
| Operation type | intermittent or continuous operation |
| Password protection | user-defined password |
| Programmability | optical interface and bcsoft software |
| Modulation actuator drive | positions the connected butterfly valve |
| Electronic ignition | integrated electronic ignition |
| Max. number of operating cycles | 250000 |
| System pressure switch monitoring | monitors gas and air pressure |
| Air pressure monitoring | Yes |
| Display | operating and display elements |
| Built-in display | operating and display elements |
| Optical interface | Yes |
| Fan support | yes |
| Internal ignition | yes |
| Supported ignition systems | directly ignited and pilot burner |
| Quick launch option | quick-start option |
| Automatic cycle | automatic gas firing device |
| Monitored inputs | gas and air pressure, flame |
| Frequency | 50–60 Hz |
| Certification | IP54 pursuant to IEC 529 |
| Fuel | Gas |
| Valve control type | on |
| Pre-purge on each start-up | on |
| Tightness control function | Yes |
| Air pressure switch model | DL |
| Flame proving period 1, burner/pilot tFS1 | 2 s |
| Flame proving period 2, main burner tFS2 | 2 s |
| Application type | industrial forced draught burners |
| Ignition type | Direct or pilot ignition |
| Weight | 1460 g |
| Post-purge | 0 |
| Minimum burner pause time tBP | 0 s |
| Burner start-up attempts | 1 |
| Switch-on delay time tE | 0 s |
| Plug-in design | plug-in upper section |
| Adjustable start-up attempts | Yes |
| Restart behavior | Automatic restart when activated |
| Pre-purge time | 60 s |
| Pre-ignition time | 1 s |
| Net weight | 1.46 kg |
2406.00EUR
in stock · 1excl. VAT · import VAT and duties on delivery · shipping calculated at checkout
- Delivery to 97 countries
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder BCU370WFEU0D3 (SKU 88600123) is a burner control unit for industrial forced draught burners with unlimited capacity. It controls, ignites, and monitors the burner in intermittent or continuous operation, supporting both ionization and UV flame detection. The unit operates on a 230 V supply at 50–60 Hz and is rated for ambient temperatures from -20 to 60 °C. It includes an integrated electronic ignition, a pre-purge time of 60 seconds, and a fault lock-out safety feature. The housing is made of impact-resistant and heat-resistant plastic, protected to IP54, and weighs 1.46 kg.
Further details
| Air Pressure Switch Verification | air pressure check during pre-purge and operation |
|---|---|
| Air pressure monitoring | during pre-purge and operation by external air pressure switch |
| Application | directly ignited forced draught burners and those ignited with a pilot burner |
| Construction type | plug-in upper section with lower section |
| Digital input function | integrated tightness control |
| Flame signal for Ionization control | 1 – 28 μA, UV control: 1 – 35 μA |
| Mains voltage | 230 V AC, 50/60 Hz |
| Plug In Design | plug-in upper section with operating and display elements |
| Wiring Chamber | lower section with connection terminals, earthing strip and pre-wired neutral bus with spacious wiring chamber |
Choosing and fitting
Parts of this type are selected by matching the control unit to the burner's ignition and flame detection arrangement (ionization or UV), the valve control type, and the required safety and purge times. The mains voltage and frequency must match the supply, and the maximum lengths of the ignition cable (1 m) and ionization/UV cable (50 m) must not be exceeded. The unit is a plug-in design with an upper section carrying the operating and display elements and a lower section with connection terminals, earthing strip and pre-wired neutral bus; the wiring chamber must accommodate the existing cable routing. Before ordering, compare the mounting and connection layout of the existing unit and confirm the ambient temperature range and enclosure rating suit the installation location.
Signs of failure
Typical failure modes include fault lock-out on flame failure, which stops the burner and requires a manual reset. If the flame signal falls below the switch-off threshold, the unit locks out during operation. Air or gas pressure monitoring faults can prevent start-up or cause lock-out during pre-purge. Check the flame detector (ionization or UV), the air pressure switch, the gas pressure switch, and the wiring to the fan and valve controls, and verify the supply voltage and cable lengths.
All specifications
| Supply voltage | 230 V |
|---|---|
| Safety time | 1 s |
| Flame detector type | UV sensor or ionisation sensor |
| Protection class (IP) | IP54 |
| Body material | impact-resistant and heat-resistant plastic |
| Flame control mode | ionization control or UV control |
| Burner capacity | unlimited capacity |
| Ambient temperature | -20–60 °C |
| Service life under maximum load | 250000 |
| Cycle type | intermittent or continuous |
| Flame detection methods supported | ionisation, UV |
| Safety feature | fault lock-out |
| Controller enable signal delay time tRF | 0 s |
| TC test period tP | 60 s |
| Fan run-up time tGV | 0 s |
| Fan control rating | 3 A |
| Maximum length of ignition cable with integrated electronic ignition | 1 m |
| Maximum length of ionisation/UV cable | 50 m |
| Air monitoring during pre-purge | on |
| Air monitoring during operation | on |
| Gas pressure monitoring | on |
| UVS check | off |
| Operating time in manual mode | 5 minutes |
| V2 during burner operation | off |
| Behaviour in the event of flame failure during operation | fault lock-out |
| Burner switch-off threshold | 1 µA |
| Operation type | intermittent or continuous operation |
| Password protection | user-defined password |
| Programmability | optical interface and bcsoft software |
| Modulation actuator drive | positions the connected butterfly valve |
| Electronic ignition | integrated electronic ignition |
| Max. number of operating cycles | 250000 |
| System pressure switch monitoring | monitors gas and air pressure |
| Air pressure monitoring | Yes |
| Display | operating and display elements |
| Built-in display | operating and display elements |
| Optical interface | Yes |
| Fan support | yes |
| Internal ignition | yes |
| Supported ignition systems | directly ignited and pilot burner |
| Quick launch option | quick-start option |
| Automatic cycle | automatic gas firing device |
| Monitored inputs | gas and air pressure, flame |
| Frequency | 50–60 Hz |
| Certification | IP54 pursuant to IEC 529 |
| Fuel | Gas |
| Valve control type | on |
| Pre-purge on each start-up | on |
| Tightness control function | Yes |
| Air pressure switch model | DL |
| Flame proving period 1, burner/pilot tFS1 | 2 s |
| Flame proving period 2, main burner tFS2 | 2 s |
| Application type | industrial forced draught burners |
| Ignition type | Direct or pilot ignition |
| Weight | 1460 g |
| Post-purge | 0 |
| Minimum burner pause time tBP | 0 s |
| Burner start-up attempts | 1 |
| Switch-on delay time tE | 0 s |
| Plug-in design | plug-in upper section |
| Adjustable start-up attempts | Yes |
| Restart behavior | Automatic restart when activated |
| Pre-purge time | 60 s |
| Pre-ignition time | 1 s |
| Net weight | 1.46 kg |
Part numbers
| SKU | 88600123 |
|---|---|
| Additional article | 624.103.111 |
| Model | BCU370WFEU0D3 |
Similar parts
1287.60 EURexcl. VAT · import VAT and duties on delivery
2661.60 EURexcl. VAT · import VAT and duties on delivery
3135.60 EURexcl. VAT · import VAT and duties on delivery
2661.60 EURexcl. VAT · import VAT and duties on delivery
2591.40 EURexcl. VAT · import VAT and duties on delivery
2661.60 EURexcl. VAT · import VAT and duties on delivery
2679.00 EURexcl. VAT · import VAT and duties on delivery