Siemens Electromechanical burner control LAL2.25

SKU LAL2.25 Brand Siemens
Siemens logo — Siemens spare parts for burners and boilers Brand Siemens
Buy Siemens Electromechanical burner control LAL2.25

Key specifications

Supply voltageAC
Safety time5 s
Interval between voltage application to terminals7.5 s
Interval between voltage switching at terminals7.5 s
Post-purge15
Fan motor start delay2.5 s
Start-up sequence duration47 s
FuelLiquid fuel
Air supplyforced draft
Cycle typeintermittent
Firing stagesmulti-stage or modulating
Safety featuremanual reset lockout
Valve control typeelectromechanical
Time after ignition (ignition transformer connected to terminal)15 s
Pre-purge time22.5 s
Pre-ignition time2.5 s
all specifications (16) ↓

1055.16EUR

in stock · 2

excl. VAT · import VAT and duties on delivery · shipping calculated at checkout

  • Delivery to 97 countries
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

This electromechanical control box starts and supervises multi-stage or modulating forced-draft oil burners with intermittent operation and manual reset lockout. It applies AC supply voltage to the fan motor after a 2.5 s delay, performs a 22.5 s pre-purge, then energizes the ignition transformer for 15 s. The safety time is 5 s; the intervals between voltage applications and between voltage switchings are 7.5 s each, and post-purge lasts 15 s. The complete start-up sequence takes 47 s, with pre-ignition time 2.5 s.

Further details

Air pressure switch verificationfunctional test of the air pressure relay during start-up and operation
Flame Detectorphotoresistive sensor (QRB1…) and selenium photocell (RAR...)

Choosing and fitting

When selecting a replacement control box of this type, match the exact series and type designation, supply voltage, required safety time, pre-purge time, and flame-detection method of the burner. Verify the voltage rating and the base or plug pattern to ensure physical fit; controls within one series are not interchangeable if the safety-time setting differs. Some burners are fitted with electronic control boards instead; those boards are matched to the boiler model and are not field-interchangeable with a traditional control box. Use the part number on the existing control as the only certain reference if the burner documentation is unavailable.

All specifications

Supply voltageAC
Safety time5 s
Interval between voltage application to terminals7.5 s
Interval between voltage switching at terminals7.5 s
Post-purge15
Fan motor start delay2.5 s
Start-up sequence duration47 s
FuelLiquid fuel
Air supplyforced draft
Cycle typeintermittent
Firing stagesmulti-stage or modulating
Safety featuremanual reset lockout
Valve control typeelectromechanical
Time after ignition (ignition transformer connected to terminal)15 s
Pre-purge time22.5 s
Pre-ignition time2.5 s

Part numbers

SKULAL2.25
Additional article884.124.005

Similar parts

Request an invoice

We issue the invoice for payment by bank transfer and send it by e-mail. Invoices are issued to companies; the EU VAT number is optional.

Delivery address

Drag the pin to the exact spot — it helps the courier find you.

Delivery

Enter the country, postcode and city to see the delivery options.

Invoice {number} has been sent to {email}. Delivery is not included in this invoice: we will confirm its cost by e-mail and send the invoice again with delivery. The invoice is also in your account under Invoices — sign in with this e-mail address. Open the invoice (PDF) Order page Close The request did not go through. Please try again. That’s all we have in stock.
1055.16 EUR 1