SKU 03155068 Model GDJ25R04-0Z Brand Kromschroder
Kromschroder logo — Kromschroder spare parts for burners and boilers Brand Kromschroder
Buy Kromschroder Gas pressure regulator GDJ25R04-0Z 03155068

Key specifications

Nominal diameter (DN)25 mm
Connection threadRp 1"
Max. inlet pressure400 mbar
Setting range5–160 mbar
Purposemaintain a constant outlet pressure
Safety featurezero closure
Temperature range-20°C to +60°C
Operating principlespring-loaded gas pressure reducer
ComplianceEN 88, EN 334, CE
Turndown10:1
Ambient temperature-20–60 °C
Weight1000 g
Safety class2
Component typeGas pressure regulators
Reliabilityproven reliability
Standard setting12.5–25 mbar
Qualitygerman quality honeywell kromschröder
Venting arrangementno vent line required
Applicationnatural gas, liquefied gas, air
Safety diaphragm ventingbuilt-in safety diaphragm
Inlet pressure compensationwith inlet pressure compensation
Vent lineno vent line required
Regulation accuracyhigh regulation accuracy
Safety standardclass a, group 2
Gas type compatibilitynatural gas, liquefied gas, air
CertificationCE
all specifications (26) ↓

413.40EUR

in stock · 1

excl. VAT · import VAT and duties on delivery · shipping calculated at checkout

  • Delivery to 97 countries
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder GDJ25R04-0Z is a spring-loaded gas pressure regulator with inlet pressure compensation, designed to maintain a constant outlet pressure. It features a built-in safety diaphragm and zero closure, and requires no vent line. Suitable for natural gas, liquefied gas, and air, it has a nominal diameter of 25 mm (Rp 1" connection), a maximum inlet pressure of 400 mbar, and an outlet pressure range of 5–160 mbar (standard setting 12.5–25 mbar). Operating temperature range is -20°C to +60°C, weight is 1000 g, and it complies with EN 88, EN 334, and CE standards.

Further details

Installation notescheck that the regulator is oriented correctly (flow direction arrow on the body) and that the vent port is not blocked
Installation notescheck that the regulator is oriented correctly (flow direction arrow on the body) and that the vent port is not blocked
Installation notescheck that the regulator is oriented correctly (flow direction arrow on the body) and that the vent port is not blocked
Maintenance Requirementeasy installation, adjustment and minimal maintenance
Maintenance notesover time, diaphragm fatigue, dirt in the pilot valve, or corrosion can cause drifting outlet pressure or leakage. many regulators allow replacement of the diaphragm or the complete cartridge without removing the body from the pipework
Maintenance notesover time, diaphragm fatigue, dirt in the pilot valve, or corrosion can cause drifting outlet pressure or leakage. many regulators allow replacement of the diaphragm or the complete cartridge without removing the body from the pipework
Maintenance notesover time, diaphragm fatigue, dirt in the pilot valve, or corrosion can cause drifting outlet pressure or leakage. many regulators allow replacement of the diaphragm or the complete cartridge without removing the body from the pipework
Replacement checkensure the new unit matches the original's connection size and pressure rating; mismatching can cause poor burner performance or unsafe operation
Replacement checkensure the new unit matches the original's connection size and pressure rating; mismatching can cause poor burner performance or unsafe operation
Replacement checkensure the new unit matches the original's connection size and pressure rating; mismatching can cause poor burner performance or unsafe operation
Typical usemedium boiler houses and heating systems; industrial burners and heat generators; gas appliances and process lines; production equipment with moderate gas consumption
Typical usemedium boiler houses and heating systems; industrial burners and heat generators; gas appliances and process lines; production equipment with moderate gas consumption
Typical usemedium boiler houses and heating systems; industrial burners and heat generators; gas appliances and process lines; production equipment with moderate gas consumption
Verification after installationalways test the lock-up pressure after servicing to confirm the regulator holds the set point correctly
Verification after installationalways test the lock-up pressure after servicing to confirm the regulator holds the set point correctly
Verification after installationalways test the lock-up pressure after servicing to confirm the regulator holds the set point correctly

Choosing and fitting

When selecting a gas pressure regulator of this type, ensure the nominal diameter and connection thread match the existing pipework (e.g., Rp 1"). Verify the maximum inlet pressure and required outlet pressure range are within the regulator's specifications. Check the gas type compatibility (natural gas, liquefied gas, air) and temperature range. Installation must follow the flow direction arrow on the body, and the vent port (if present) must not be blocked. For regulators without a vent line, ensure the built-in safety diaphragm is intact.

Signs of failure

Common failures include diaphragm fatigue, dirt in the pilot valve, or corrosion, leading to drifting outlet pressure or leakage. Symptoms may include unstable burner operation, fluctuating gas pressure, or failure to maintain set point. Check the regulator for proper lock-up pressure after servicing, and inspect the diaphragm and valve seat for wear or contamination.

All specifications

Nominal diameter (DN)25 mm
Connection threadRp 1"
Max. inlet pressure400 mbar
Setting range5–160 mbar
Purposemaintain a constant outlet pressure
Safety featurezero closure
Temperature range-20°C to +60°C
Operating principlespring-loaded gas pressure reducer
ComplianceEN 88, EN 334, CE
Turndown10:1
Ambient temperature-20–60 °C
Weight1000 g
Safety class2
Component typeGas pressure regulators
Reliabilityproven reliability
Standard setting12.5–25 mbar
Qualitygerman quality honeywell kromschröder
Venting arrangementno vent line required
Applicationnatural gas, liquefied gas, air
Safety diaphragm ventingbuilt-in safety diaphragm
Inlet pressure compensationwith inlet pressure compensation
Vent lineno vent line required
Regulation accuracyhigh regulation accuracy
Safety standardclass a, group 2
Gas type compatibilitynatural gas, liquefied gas, air
CertificationCE

Part numbers

SKU03155068
Additional article624.658.055
ModelGDJ25R04-0Z

Similar parts

Request an invoice

We issue the invoice for payment by bank transfer and send it by e-mail. Invoices are issued to companies; the EU VAT number is optional.

Delivery address

Drag the pin to the exact spot — it helps the courier find you.

Delivery

Enter the country, postcode and city to see the delivery options.

Invoice {number} has been sent to {email}. Delivery is not included in this invoice: we will confirm its cost by e-mail and send the invoice again with delivery. The invoice is also in your account under Invoices — sign in with this e-mail address. Open the invoice (PDF) Order page Close The request did not go through. Please try again. That’s all we have in stock.
413.40 EUR 1