Honeywell Control unit DVI980-N mod. 02 0490602U

SKU 0490602U Model DVI980-N mod. 02 Brand Honeywell
Honeywell logo — Honeywell spare parts for burners and boilers Brand Honeywell
Buy Honeywell Control unit DVI980-N mod. 02 0490602U

Key specifications

Supply voltage220–240 V
Protection class (IP)IP40
Spark energy10 mJ
Ignition transformer voltage20 kV
Sensitivity1.0 µA
Min. required ion. current1.5 µA
Sensitivity for stray light0.4 µA
Weight incl. wiring base190 kg
Installation positionany
Mounting positionany
Net weight0.19 kg
all specifications (11) ↓

154.01EUR

in stock · 2

excl. VAT · import VAT and duties on delivery · shipping calculated at checkout

  • Delivery to 97 countries
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Honeywell DVI980-N mod. 02 control box is a control unit designed for 1-stage forced draught and atmospheric gas burners, capable of operating with DC valves. It supports flame detection via an ionization probe, infrared flicker detector (IRD 1020.1), or UV flame sensor (UVD 971). The unit operates at a supply voltage of 220–240 V, provides ignition spark energy of 10 mJ at 20 kV, and has a sensitivity of 1.0 µA with a minimum required ion current of 1.5 µA. It weighs 0.19 kg net (190 g including wiring base) and has an IP40 protection class. The control box can be installed in any position.

Further details

Air proving switch1 working contact
Cable length< 3 m
Flame Detectorionisation probe, infrared flicker detector 1020.1, uv flame sensor uvd 971
Flame detectors IRD 1020.1end-on viewing
Flame signal outputOptocoupler max 70V DC/100mA
Ignition frequencyup to 40 Hz
Mounting positionany
Power consumptionca. 12 VA
Protection classIP 40
STB Safety temperature delimiter1 working contact
Stray capacityProbe - earth less than 1000 pF
Total loadmax. 6 A during 0,5 sec
UVD 971end-on viewing

Choosing and fitting

When selecting a control box of this type, ensure the supply voltage matches the burner's electrical system (e.g., 220–240 V). Verify the flame detector type (ionization probe, IR, or UV) is compatible with the control box's input specifications. Check the ignition voltage and spark energy requirements of the burner to match the control box's output. The mounting position is flexible, but the wiring base must be correctly connected according to the manufacturer's diagram. Always compare the control box's sensitivity and ion current thresholds with the burner's flame characteristics.

Signs of failure

Common failure modes for this type of control box include failure to ignite, intermittent flame loss, or no response to flame signals. Symptoms may include the burner not starting, locking out after repeated ignition attempts, or shutting down during operation. Check the ignition transformer, flame detector, and wiring connections for faults. Verify that the ion current or UV/IR signal is within the required range, and inspect for loose connections or damaged components.

All specifications

Supply voltage220–240 V
Protection class (IP)IP40
Spark energy10 mJ
Ignition transformer voltage20 kV
Sensitivity1.0 µA
Min. required ion. current1.5 µA
Sensitivity for stray light0.4 µA
Weight incl. wiring base190 kg
Installation positionany
Mounting positionany
Net weight0.19 kg

Part numbers

SKU0490602U
Additional article852.124.213
ModelDVI980-N mod. 02

Similar parts

Request an invoice

We issue the invoice for payment by bank transfer and send it by e-mail. Invoices are issued to companies; the EU VAT number is optional.

Delivery address

Drag the pin to the exact spot — it helps the courier find you.

Delivery

Enter the country, postcode and city to see the delivery options.

Invoice {number} has been sent to {email}. Delivery is not included in this invoice: we will confirm its cost by e-mail and send the invoice again with delivery. The invoice is also in your account under Invoices — sign in with this e-mail address. Open the invoice (PDF) Order page Close The request did not go through. Please try again. That’s all we have in stock.
154.01 EUR 1