excl. VAT · import VAT and duties on delivery
· shipping calculated at checkout
Delivery to 97 countries
Original manufacturer part
Dispatch within 24 h for stocked items
Description
Ignition transformer for automatic ignition systems in gas and liquid fuel burners. It operates at 230 V supply and generates the high voltage needed to produce a spark. The compact housing suits installations in boiler equipment, industrial burners, and thermal installations. This unit corresponds to model COMPACT 8/10CM CON 230V and SKU TE081D.
Further details
Application
boiler equipment, industrial burners, and thermal installations
Operating Phase
ignition phase, under command from the burner control
Choosing and fitting
Parts of this type are selected by matching primary voltage, secondary voltage and current, duty cycle, mounting arrangement, terminal type, and the connector pattern for the high-voltage cable. The high-voltage cable must be silicone-insulated to withstand extreme voltage and heat. Ensure the replacement matches the original mounting footprint and that the cable connector fits the electrode lead.
Signs of failure
Common failure modes include a weak spark or internal leakage, often caused by a hardened or cracked high-voltage cable leaking spark to ground. When the transformer or cable fails, ignition does not occur and the burner control may lock out. Before replacing the transformer, check the condition of the high-voltage cable and the electrode gap.