excl. VAT · import VAT and duties on delivery
· shipping calculated at checkout
Delivery to 97 countries
Original manufacturer part
Dispatch within 24 h for stocked items
Description
This ignition transformer, SKU ENTBC32, is a step-up transformer used in the Fida 26/35 50% ITAQ burner. It raises the mains voltage to a level sufficient to create a spark across the ignition electrode gap. The unit is energised only during the ignition period under command from the burner control, and is switched off once flame is established. It operates with a three-core power cable of 1140 mm length, which connects the transformer to the burner manager.
Further details
Operating Phase
energised only during the ignition period
Choosing and fitting
This type of ignition transformer is selected by secondary voltage and current, primary voltage (typically 230 V, with 110 V and 24 V variants), duty cycle, mounting and terminal pattern, and connector layout. Before installing a replacement, check that the high-voltage cable has silicone insulation and is not hardened or cracked; such damage can leak spark to earth. Confirm that the transformer is correctly earthed and that the electrode gap is set to the burner manufacturer's specification.
Signs of failure
A no-flame condition on the burner can be caused by a hardened or cracked high-voltage cable that leaks the spark to earth. This symptom mimics transformer failure, so inspect the cable before deciding to replace the transformer.