Gas solenoid valves and coils: Kromschröder, Dungs and others
The valve opens the gas, the coil opens the valve. When one of them fails the burner does not start, and the part number on the plate is the only reliable way to find the replacement.
How a gas solenoid valve works
A solenoid valve is closed by a spring and opened by a coil. When the burner control applies voltage, the coil lifts the plunger and the gas flows. When the voltage is removed, the spring closes the valve. For safety, a burner has two valves in series, and they are often built into one housing as a double solenoid valve. Each valve has its own coil.
Reading a Kromschröder VAS type key
Kromschröder's VAS solenoid valve for gas is the most common type in our catalogue. The type key, as given in the operating instructions, is built like this:
| Part of the key | Meaning |
|---|---|
| VAS | Solenoid valve for gas |
| 1 to 3, or 6 to 9 | Size |
| 10 to 65 | Nominal size of the inlet and outlet flange or thread |
| R | Internal thread, Rp |
| N | Fast opening: within 0.5 seconds |
| L | Slow opening: within 10 seconds |
The maximum inlet pressure depends on the version, so it is read from the data sheet of the exact type and not guessed from the size. For example, listings for some VAS 1 and VAS 2 valves state 500 mbar.
Replacing a coil
A burnt or open coil is a common failure and the coil is usually a separate part. Dungs' instructions for their solenoids give the order: remove the solenoid by pulling it straight up, note the solenoid number and the voltage, and check that the replacement has the same number and the same electrical rating. After reassembly a function test is required.
A coil with the wrong voltage burns out or does not lift the plunger. A coil of the right voltage but the wrong type may not fit or may have a different power. On a Kromschröder, Dungs, Weishaupt or Giersch valve the number is on the coil itself and on the plate of the valve.
After any work on a gas valve
Every joint that was opened has to be tested for tightness, and the valve has to be checked for function before the burner is put back in service. This is work for a qualified gas technician, and the burner manufacturer's manual and the local rules apply.
In the catalogue
Gas solenoid valves, double valves and coils are in the gas valves and coils section. Send us the number from the old coil or the plate of the valve and we will tell you whether we have it.
Sources: Kromschröder (Elster), solenoid valves for gas VAS, VCS, operating instructions and technical information; Karl Dungs, solenoid valve operating instructions.