Danfoss Oil nozzle 0.85GPH,60B 030B0106

SKU 030B0106 Brand Danfoss

Photos

no photo yet

Key specifications

Flow rate0.85 GPH
Spray angle60 °
Spray patternB
all specifications (3) ↓
price on request
on order

shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items
Specifications

Description

This is a Danfoss oil nozzle with a flow rate of 0.85 GPH, a 60° spray angle, and a B spray pattern. It is used in oil burners to atomise fuel into a fine spray for combustion. The 0.85 GPH rating defines the volume of oil delivered per hour at the rated pressure. The 60° angle sets the width of the spray cone, and the B pattern denotes a solid spray shape. The SKU for this item is 030B0106.

Nozzle selection chart

Flow rate kg/h 30°45°60°80°
0.30 0.95 HS HS
0.35 1.11 S S
0.40 1.27 S HS HS
0.45 1.43 S S HS
0.50 1.59 S S HS HS
0.55 1.75 S HS HS
0.60 1.91 S HS BHS BHS
0.65 2.07 BS BHS BHS
0.75 2.38 S BS BHS BHSSR
0.85 2.70 S BHS BHSSR BHS
1.00 3.18 S BS BHS BHS
1.10 3.50 S HS S
1.20 3.82 S HS S
1.25 3.97 S BS BHS BHS
1.35 4.29 BS BHS BHS
1.50 4.77 S BS BHS BHS
1.65 5.25 S HS HS
1.75 5.56 S S HS S
2.00 6.36 S BS BHS BHS
2.25 7.15 S BS BHS S
2.50 7.95 S BS BHS BS
2.75 8.74 BS BHS HS
3.00 9.54 S BS BHS BHS
3.50 11.13 S S S
3.75 11.92 B B B
4.00 12.72 S S S
4.50 14.31 BS BS BS
5.00 15.90 BS BS BS
5.50 17.49 BS BS BS
6.00 19.08 BS BS BS
6.50 20.67 B B B
7.00 22.26 S
7.50 23.85 B B B
8.00 25.44 S
8.50 27.02 B B B
9.00 28.61 S
10.00 31.79 B B B
11.00 34.97 B B B
12.00 38.15 B B B
13.50 42.92 B B B
15.00 47.69 B B B
17.00 54.05 B B
19.50 62.00 B B
22.00 69.95 B B B
25.00 79.49 B B
28.00 89.02 B B
31.50 100.15 B B B
35.00 111.28 B

Choosing and fitting

Nozzles of this type are selected by matching the flow rate, spray angle, and spray pattern to the burner manufacturer's specification. The mounting form must also match: the nozzle body, thread, and sealing face must fit the burner's nozzle adapter. Before ordering, compare the existing nozzle's markings and dimensions with the replacement, and verify the pump pressure at which the flow rate is rated. If the adapter or seat is damaged, it must be replaced as well.

Signs of failure

Nozzles of this kind can clog, wear at the orifice, or develop a distorted spray pattern over time. When this happens, the burner may produce a smoky flame, fail to ignite, pulsate, or show a drop in heat output. Check for carbon deposits on the nozzle face, a worn or enlarged orifice, and a spray pattern that is asymmetric or dripping rather than finely atomised.

All specifications

Flow rate0.85 GPH
Spray angle60 °
Spray patternB

Part numbers

SKU030B0106