Danfoss Oil nozzle 25.00GPH,80B 030B0251

SKU 030B0251 Brand Danfoss

Photos

no photo yet

Key specifications

Flow rate25 GPH
Spray angle80 °
Spray patternB
all specifications (3) ↓
price on request
on order

shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items
Specifications

Description

This is a Danfoss oil nozzle with a flow rate of 25 GPH, a spray angle of 80°, and a spray pattern of B. It is used in oil burners to atomise fuel oil into a fine spray for combustion. The 80° spray angle determines the shape of the flame, while the B pattern denotes a solid spray cone. The nozzle is identified by SKU 030B0251.

Nozzle selection chart

Flow rate kg/h 30°45°60°80°
0.30 0.95 HS HS
0.35 1.11 S S
0.40 1.27 S HS HS
0.45 1.43 S S HS
0.50 1.59 S S HS HS
0.55 1.75 S HS HS
0.60 1.91 S HS BHS BHS
0.65 2.07 BS BHS BHS
0.75 2.38 S BS BHS BHSSR
0.85 2.70 S BHS BHSSR BHS
1.00 3.18 S BS BHS BHS
1.10 3.50 S HS S
1.20 3.82 S HS S
1.25 3.97 S BS BHS BHS
1.35 4.29 BS BHS BHS
1.50 4.77 S BS BHS BHS
1.65 5.25 S HS HS
1.75 5.56 S S HS S
2.00 6.36 S BS BHS BHS
2.25 7.15 S BS BHS S
2.50 7.95 S BS BHS BS
2.75 8.74 BS BHS HS
3.00 9.54 S BS BHS BHS
3.50 11.13 S S S
3.75 11.92 B B B
4.00 12.72 S S S
4.50 14.31 BS BS BS
5.00 15.90 BS BS BS
5.50 17.49 BS BS BS
6.00 19.08 BS BS BS
6.50 20.67 B B B
7.00 22.26 S
7.50 23.85 B B B
8.00 25.44 S
8.50 27.02 B B B
9.00 28.61 S
10.00 31.79 B B B
11.00 34.97 B B B
12.00 38.15 B B B
13.50 42.92 B B B
15.00 47.69 B B B
17.00 54.05 B B
19.50 62.00 B B
22.00 69.95 B B B
25.00 79.49 B B
28.00 89.02 B B
31.50 100.15 B B B
35.00 111.28 B

Choosing and fitting

Nozzles of this type are selected by matching the flow rate, spray angle, and spray pattern to the burner manufacturer's specification. The mounting thread and nozzle body dimensions must also match the nozzle holder. Before ordering, compare the markings on the existing nozzle with the required specification. Installation requires the correct tightening torque and a clean seating surface to avoid leaks.

Signs of failure

Nozzles of this kind commonly fail by clogging, wear of the orifice, or a distorted spray pattern. When this happens, the burner may produce a smoky flame, run roughly, or fail to ignite. Check for carbon deposits on the nozzle tip and verify the spray pattern during servicing.

All specifications

Flow rate25 GPH
Spray angle80 °
Spray patternB

Part numbers

SKU030B0251