Danfoss Oil nozzle 3.50GPH,45S 030F4142

SKU 030F4142 Brand Danfoss

Photos

no photo yet

Key specifications

Flow rate3.5 GPH
Spray angle45 °
Spray patternS
all specifications (3) ↓
price on request
on order

shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items
Specifications

Description

This is a Danfoss oil nozzle with SKU 030F4142. It has a flow rate of 3.5 GPH, a 45 ° spray angle, and an S spray pattern. It is used to atomise fuel oil in a burner's combustion chamber. The S spray pattern produces a solid cone of atomised oil. The 45 ° angle sets the width of the spray cone.

Nozzle selection chart

Flow rate kg/h 30°45°60°80°
0.30 0.95 HS HS
0.35 1.11 S S
0.40 1.27 S HS HS
0.45 1.43 S S HS
0.50 1.59 S S HS HS
0.55 1.75 S HS HS
0.60 1.91 S HS BHS BHS
0.65 2.07 BS BHS BHS
0.75 2.38 S BS BHS BHSSR
0.85 2.70 S BHS BHSSR BHS
1.00 3.18 S BS BHS BHS
1.10 3.50 S HS S
1.20 3.82 S HS S
1.25 3.97 S BS BHS BHS
1.35 4.29 BS BHS BHS
1.50 4.77 S BS BHS BHS
1.65 5.25 S HS HS
1.75 5.56 S S HS S
2.00 6.36 S BS BHS BHS
2.25 7.15 S BS BHS S
2.50 7.95 S BS BHS BS
2.75 8.74 BS BHS HS
3.00 9.54 S BS BHS BHS
3.50 11.13 S S S
3.75 11.92 B B B
4.00 12.72 S S S
4.50 14.31 BS BS BS
5.00 15.90 BS BS BS
5.50 17.49 BS BS BS
6.00 19.08 BS BS BS
6.50 20.67 B B B
7.00 22.26 S
7.50 23.85 B B B
8.00 25.44 S
8.50 27.02 B B B
9.00 28.61 S
10.00 31.79 B B B
11.00 34.97 B B B
12.00 38.15 B B B
13.50 42.92 B B B
15.00 47.69 B B B
17.00 54.05 B B
19.50 62.00 B B
22.00 69.95 B B B
25.00 79.49 B B
28.00 89.02 B B
31.50 100.15 B B B
35.00 111.28 B

Choosing and fitting

Nozzles of this type are selected by matching the flow rate, spray angle, and spray pattern to the burner manufacturer's specification. The mounting form must also match: check the thread size, the length and diameter of the nozzle body, and the sealing face against the nozzle holder. Before ordering, compare the markings on the old nozzle with the required values and confirm that the nozzle seats correctly in its holder without leaks.

Signs of failure

Nozzles of this kind commonly fail by clogging, wear of the orifice, or a distorted spray pattern. When this happens, the burner may produce a poor flame, smoke, soot, or fail to ignite, and the combustion readings can drift from the set values. Check the nozzle for blockage, damage, and spray shape, and compare the flow rate and pattern with the specification.

All specifications

Flow rate3.5 GPH
Spray angle45 °
Spray patternS

Part numbers

SKU030F4142