Key specifications

Flow rate13.5 GPH
Spray angle80 °
Spray patternB
all specifications (3) ↓
price on request
on order

shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items
Specifications

Description

The Danfoss 030B0241 is an oil nozzle with a flow rate of 13.5 GPH, a spray angle of 80°, and a B spray pattern. It is used in oil burners to atomise fuel into a fine spray for combustion. The 80° angle defines the shape of the spray cone, while the B pattern denotes the distribution of fuel within that cone. The 13.5 GPH rating states the volume of oil the nozzle passes per hour at its rated pressure.

Nozzle selection chart

Flow rate kg/h 30°45°60°80°
0.30 0.95 HS HS
0.35 1.11 S S
0.40 1.27 S HS HS
0.45 1.43 S S HS
0.50 1.59 S S HS HS
0.55 1.75 S HS HS
0.60 1.91 S HS BHS BHS
0.65 2.07 BS BHS BHS
0.75 2.38 S BS BHS BHSSR
0.85 2.70 S BHS BHSSR BHS
1.00 3.18 S BS BHS BHS
1.10 3.50 S HS S
1.20 3.82 S HS S
1.25 3.97 S BS BHS BHS
1.35 4.29 BS BHS BHS
1.50 4.77 S BS BHS BHS
1.65 5.25 S HS HS
1.75 5.56 S S HS S
2.00 6.36 S BS BHS BHS
2.25 7.15 S BS BHS S
2.50 7.95 S BS BHS BS
2.75 8.74 BS BHS HS
3.00 9.54 S BS BHS BHS
3.50 11.13 S S S
3.75 11.92 B B B
4.00 12.72 S S S
4.50 14.31 BS BS BS
5.00 15.90 BS BS BS
5.50 17.49 BS BS BS
6.00 19.08 BS BS BS
6.50 20.67 B B B
7.00 22.26 S
7.50 23.85 B B B
8.00 25.44 S
8.50 27.02 B B B
9.00 28.61 S
10.00 31.79 B B B
11.00 34.97 B B B
12.00 38.15 B B B
13.50 42.92 B B B
15.00 47.69 B B B
17.00 54.05 B B
19.50 62.00 B B
22.00 69.95 B B B
25.00 79.49 B B
28.00 89.02 B B
31.50 100.15 B B B
35.00 111.28 B

Choosing and fitting

Nozzles of this type are selected by matching the flow rate, spray angle, and spray pattern to the burner's requirements, and by confirming the thread and mounting form suit the nozzle holder. The spray angle must suit the combustion chamber geometry, and the pattern must match the air flow arrangement. Before ordering, compare the markings on the existing nozzle with the required specification.

Signs of failure

Nozzles of this kind commonly fail through clogging of the orifice or internal filter, wear that enlarges the orifice and raises flow rate, or a distorted spray pattern from deposits or damage. The equipment may then show poor combustion, smoke, soot deposits, unstable flame, or difficulty igniting. Check the spray pattern, flow rate, and the condition of the filter and orifice, and replace the nozzle if the spray is uneven or the flow is out of specification.

All specifications

Flow rate13.5 GPH
Spray angle80 °
Spray patternB

Part numbers

SKU030B0241