Danfoss Oil nozzle 0.75GPH,80SR 030F9916

SKU 030F9916 Brand Danfoss

Photos

no photo yet

Key specifications

Flow rate0.75 GPH
Spray angle80 °
Spray patternSR
all specifications (3) ↓
price on request
on order

shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items
Specifications

Description

This is an oil nozzle with a flow rate of 0.75 GPH, a spray angle of 80°, and an SR spray pattern. It is used in oil burners to atomise fuel into a fine spray for combustion. The 80° angle defines the width of the spray cone, and the SR pattern determines the shape of the spray. The nozzle is identified by SKU 030F9916.

Nozzle selection chart

Flow rate kg/h 30°45°60°80°
0.30 0.95 HS HS
0.35 1.11 S S
0.40 1.27 S HS HS
0.45 1.43 S S HS
0.50 1.59 S S HS HS
0.55 1.75 S HS HS
0.60 1.91 S HS BHS BHS
0.65 2.07 BS BHS BHS
0.75 2.38 S BS BHS BHSSR
0.85 2.70 S BHS BHSSR BHS
1.00 3.18 S BS BHS BHS
1.10 3.50 S HS S
1.20 3.82 S HS S
1.25 3.97 S BS BHS BHS
1.35 4.29 BS BHS BHS
1.50 4.77 S BS BHS BHS
1.65 5.25 S HS HS
1.75 5.56 S S HS S
2.00 6.36 S BS BHS BHS
2.25 7.15 S BS BHS S
2.50 7.95 S BS BHS BS
2.75 8.74 BS BHS HS
3.00 9.54 S BS BHS BHS
3.50 11.13 S S S
3.75 11.92 B B B
4.00 12.72 S S S
4.50 14.31 BS BS BS
5.00 15.90 BS BS BS
5.50 17.49 BS BS BS
6.00 19.08 BS BS BS
6.50 20.67 B B B
7.00 22.26 S
7.50 23.85 B B B
8.00 25.44 S
8.50 27.02 B B B
9.00 28.61 S
10.00 31.79 B B B
11.00 34.97 B B B
12.00 38.15 B B B
13.50 42.92 B B B
15.00 47.69 B B B
17.00 54.05 B B
19.50 62.00 B B
22.00 69.95 B B B
25.00 79.49 B B
28.00 89.02 B B
31.50 100.15 B B B
35.00 111.28 B

Choosing and fitting

Nozzles of this type are selected by matching the flow rate, spray angle, and spray pattern to the burner's requirements. The mounting thread and the length of the nozzle body must match the nozzle holder on the burner. Before ordering, compare the markings on the old nozzle with the required specification. The spray pattern and angle must suit the combustion chamber shape and the burner's air flow.

Signs of failure

Nozzles of this kind can clog, wear at the orifice, or develop a distorted spray pattern over time. When this happens, the burner may produce a smoky flame, fail to ignite, or run unevenly. A blocked or worn nozzle can also cause pulsating combustion or a visible drip of oil. Checking the spray pattern and flow rate against the specification helps identify a failed nozzle.

All specifications

Flow rate0.75 GPH
Spray angle80 °
Spray patternSR

Part numbers

SKU030F9916