Danfoss Oil nozzle 28.00GPH,60B 030B0153

SKU 030B0153 Brand Danfoss

Photos

no photo yet

Key specifications

Flow rate28 GPH
Spray angle60 °
Spray patternB
all specifications (3) ↓
price on request
on order

shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items
Specifications

Description

This is a Danfoss oil nozzle with a flow rate of 28 GPH, a 60° spray angle, and a B spray pattern. It is used to atomise fuel oil in a burner, producing the spray that is ignited in the combustion chamber. The 60° angle defines the cone width of the spray, and the B pattern denotes the distribution of fuel within that cone. The 28 GPH rating states the volume of oil the nozzle passes per hour at its rated pressure. It is identified by the SKU 030B0153.

Nozzle selection chart

Flow rate kg/h 30°45°60°80°
0.30 0.95 HS HS
0.35 1.11 S S
0.40 1.27 S HS HS
0.45 1.43 S S HS
0.50 1.59 S S HS HS
0.55 1.75 S HS HS
0.60 1.91 S HS BHS BHS
0.65 2.07 BS BHS BHS
0.75 2.38 S BS BHS BHSSR
0.85 2.70 S BHS BHSSR BHS
1.00 3.18 S BS BHS BHS
1.10 3.50 S HS S
1.20 3.82 S HS S
1.25 3.97 S BS BHS BHS
1.35 4.29 BS BHS BHS
1.50 4.77 S BS BHS BHS
1.65 5.25 S HS HS
1.75 5.56 S S HS S
2.00 6.36 S BS BHS BHS
2.25 7.15 S BS BHS S
2.50 7.95 S BS BHS BS
2.75 8.74 BS BHS HS
3.00 9.54 S BS BHS BHS
3.50 11.13 S S S
3.75 11.92 B B B
4.00 12.72 S S S
4.50 14.31 BS BS BS
5.00 15.90 BS BS BS
5.50 17.49 BS BS BS
6.00 19.08 BS BS BS
6.50 20.67 B B B
7.00 22.26 S
7.50 23.85 B B B
8.00 25.44 S
8.50 27.02 B B B
9.00 28.61 S
10.00 31.79 B B B
11.00 34.97 B B B
12.00 38.15 B B B
13.50 42.92 B B B
15.00 47.69 B B B
17.00 54.05 B B
19.50 62.00 B B
22.00 69.95 B B B
25.00 79.49 B B
28.00 89.02 B B
31.50 100.15 B B B
35.00 111.28 B

Choosing and fitting

Nozzles of this type are selected by matching the flow rate, spray angle, and spray pattern to the burner's requirements, and by confirming the thread and body dimensions fit the nozzle holder. Mounting forms vary by burner design, so the seat, thread size, and overall length must be compared with the old part before ordering. The rated pressure at which the flow rate is specified must also match the pump setting.

Signs of failure

Nozzles of this kind commonly fail by clogging, wear of the orifice, or a distorted spray pattern. When this happens the burner may show a weak or uneven flame, delayed ignition, soot deposits, or a rise in flue gas readings. Checks include the spray pattern on a test stand, the flow rate against the rated value, and the condition of the nozzle seat and filter.

All specifications

Flow rate28 GPH
Spray angle60 °
Spray patternB

Part numbers

SKU030B0153